A building that heats with almost nothing. Remarkable comfort in every season. And a construction logic built on five rules.
The paradox of the passive house: in seeking to reduce energy consumption, what you get above all is remarkable comfort. No cold draughts near windows. No cold surfaces. Constant air quality.
In front of the glazing, the radiant temperature does not fall, by calculation, below 17 to 18 °C in the depths of winterPHI v10c, § 2.4.5: for windows, radiant temperature 0.5 m in front of the glazing no more than 4.2 K below operative, checked in PHPP at 22 °C (≈ 17.8 °C); floor ≥ 19 °C.Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — § 2.4.5 Minimum thermal protection — eliminating the cold-surface sensation typical of ordinary buildings.

The idea is radical in its simplicity: instead of offsetting heat losses with a large heating system, you start by eliminating them. A very well insulated envelope, free of defects, captures solar heat and heat from the occupants — and retains it.
The result: a building that can do without conventional heating, or almost. The heat given off by occupants, electrical appliances and the sun covers a large share of the losses; the remainder can be supplied through the ventilation supply air, with no radiator network — that is the Passivhaus Institut's functional definitionPassipedia, definition: 'thermal comfort in winter can be achieved solely by heating the supply air required for hygienic reasons' — hence a heating load of about 10 W/m².Passipedia — Passive House Institute — The Passive House – definition.

First passive house in France, 2006. Large south-facing windows, timber frame structure, louvre solar shading.
The Passivhaus standard rests on five construction principles. The Passivhaus Institut itself checks four criteria on the building: heating demand (or heating load), cooling demand, airtightness and renewable primary energyPHI v10c, Table 1: heating demand ≤ 15 kWh/(m²a) or heating load ≤ 10 W/m²; cooling + dehumidification; n50 ≤ 0.6 h⁻¹; renewable primary energy (PER). U, Uw and η are in Table 2.Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — Tableau 1. Two of the five principles coincide with those criteria — heating demand and airtightness; the other three are the component target values for a cool-temperate climate, as the Passivhaus Institut (PHI) — the Darmstadt institute that defines the passive standard and certifies buildings, directly or through accredited certifiers — sets them in Table 2 of its criteria — the EnerPHit component method. It is this overall coherence that guarantees performance.
The five symbols, in plain words. U is the thermal transmittance of a finished building element: the heat that passes through one square metre per degree of temperature difference — the lower it is, the better the element insulates. Uw is the same figure for the whole window, glazing and frame included; the PHI criterion applies to the installed window (installed Uw), installation thermal bridge included. η (eta) is the heat recovery efficiency of the ventilation system: the share of the outgoing air's heat returned to the incoming air. n₅₀ is the number of times the building's whole air volume is exchanged in one hour during a 50-pascal pressurisation test — the measure of airtightness. ψ (psi) is the extra heat loss of a thermal bridge, per metre of junction and per degree of temperature difference.
Heat recovery ventilation (HRV) deserves particular attention: often misunderstood, it is inseparable from the passive standard. It continuously renews the air while recovering the heat from the extracted air — which sharply reduces ventilation heat losses without eliminating them: the criterion above requires at least 75 % to be recovered.
Heating demand is expressed in kWh per square metre per year.
Read these as orders of magnitude: the energy reference area is not calculated the same way from one standard to the next.
Two quantities of different kinds: the Geneva IDC threshold (IDC — heating expenditure index) is a metered consumption, heating and hot water included; the Passivhaus value is a calculated heating demand, on a different reference areaPHI v10c, Table 1, note 1: the 15 kWh/(m²a) threshold is a demand calculated in PHPP, referred to the TFA. It does not compare directly with a metered heating + hot water consumption such as the IDC.Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — Tableau 1, note 1. Minergie sets no absolute value and is therefore not shown: for new builds, ≤ 90 % of the MoPEC 2025 limitMinergie regulation 2026.1, cl. 6.1: Qh (SIA 380/1:2016) ≤ 90 % of the MoPEC 2025 Qh,li for new Minergie buildings, ≤ 70 % for Minergie-P; minimum 15 kWh/(m²a). No "30–40" figure appears in it.Association Minergie — Règlement des labels MINERGIE®/MINERGIE-P®/MINERGIE-A®, Version 2026.1, ch. 6.1. Plus and Premium share the same heating threshold as Classic: they differ in renewable primary energy (PER ≤ 45 and ≤ 30 kWh/m²·yr) and renewable energy generation (≥ 60 and ≥ 120 kWh/m²·yr)PHI Criteria v10c, Table 1: PER ≤ 60 / 45 / 30 kWh/(m²a) and renewable generation ≥ – / 60 / 120 kWh/(m²a) for Classic / Plus / Premium. No class is defined as "energy-positive".Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — Tableau 1. MoPEC — the cantons' model energy regulations — is the common baseline from which each canton derives its own energy act: it is not a directly applicable federal standard.
What these 15 kWh/m²·yr are, and are not. This is a calculated space heating demand, related to the reference floor area: it includes neither domestic hot water, nor appliance electricity, nor lighting. It is therefore not the figure you will read on your bill, and it does not compare directly with a Minergie indicator or with metered consumption.
Passivhaus or Minergie-P? Both aim at the same level of performance by two different calculation routes: Passivhaus sets an absolute heating demand — ≤ 15 kWh/m²·yrPHI Criteria v10c, Table 1: heating demand ≤ 15 kWh/(m²a) referred to the TFA, OR alternatively heating load ≤ 10 W/m². The same threshold applies to Classic, Plus and Premium.Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — Tableau 1 —, Minergie-P a percentage: ≤ 70 % of MoPEC 2025 limit values, whose cantonal transposition is under wayMinergie regulation 2026.1, cl. 6.1, table: Minergie-P ≤ 70 % of the MoPEC 2025 Qh,li for new build and ≤ 90 % for retrofits, all building categories, with a floor of 15 kWh/(m²a).Association Minergie — Règlement des labels MINERGIE®/MINERGIE-P®/MINERGIE-A®, Version 2026.1, ch. 6.1, and prohibits fossil fuels for heating and domestic hot water, with exceptions (regulation 2026.1)Minergie regulation 2026.1, cl. 8.1: fossil fuels banned for heating and hot water, with four derogations (peak load, CHP, district heating ≤ 50 % fossil, grid electricity).Association Minergie — Règlement des labels MINERGIE®/MINERGIE-P®/MINERGIE-A®, Version 2026.1, ch. 8.1. Which of the two to aim for, what each actually requires and how equivalence is demonstrated is the subject of the Energy labels → dossier.
Retrofitting to the passive standard is possible, but the constraints of existing buildings — geometry, structure, unavoidable thermal bridges — call for adaptations. The EnerPHit standard (Passivhaus Institut) and Minergie®-P, with its own retrofit requirements, define specific targets.
EnerPHit target : ≤ 25 kWh/m²·yrPHI Criteria v10c, Table 3 (heating demand method): 25 kWh/(m²a) in a cool-temperate climate. By zone: 35 arctic, 30 cold, 20 warm-temperate, 15 warm.Passive House Institute (PHI), Darmstadt — Criteria for Buildings — Passive House, EnerPHit, PHI Low Energy Building, version 10c — Tableau 3. According to the Passivhaus Institut, heating savings of 75 to 90% are achievable in retrofitsPassipedia, EnerPHit page: 'Significant heating/cooling energy savings of between 75 and 90 % can be achieved even in existing buildings' [Bastian 2022]. Achievable, not guaranteed.Passipedia — Passive House Institute — EnerPHit – the Passive House Certificate for retrofits.
Valid for any new build or high-performance energy retrofit: the logic of the five pillars remains the guiding thread.

Retrofit in progress: insulation and careful attention to envelope details determine the final performance.
GenevaIn Geneva every new build must reach at least the legal HPE standard. The very high standard (THPE) is recognised for new builds holding the Minergie-A or Minergie-P-Eco label “or any other equivalent label” (REn art. 12C para. 1): Passivhaus is not named there.
SwitzerlandMinergie-P is the Swiss label closest to Passivhaus. Its thresholds are percentages of MoPEC limit values, not absolute kWh: the figures do not overlay.
Neighbouring FranceIn neighbouring France the passive standard is not compulsory: RE2020 applies there, and a Passivhaus building must meet it like any other: it also regulates the carbon impact of construction, which the label does not address.
Every figure and every claim in this dossier links back to its source. Hover or tap a footnote marker to see it.
Advice on your project and arbitration between the standards — let's talk about it, ideally from the sketch stage.
Get in touch